GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
228
Error judgment condition and method:
If the mainboard detects that input power cord voltage is lower than 320V, it will report low voltage
protection.
Possible reason
Power supply voltage is lower than 320V;
Compressor drive board is abnormal.
Troubleshooting:
2.2.4.130 PJ Inverter compressor startup failure
Error display:
ODU mainboard will display
Check the error code on nixie tube of ODU main control board. If PJ is displayed, it indicates
inverter compressor startup failure
Poor contact of compressor UVW wire;
Compressor is broken;
Compressor drive board is broken;