GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
230
2.2.4.131 U0 Insufficient compressor preheating time
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
If it is detected that the oil temperature preheating time of compressor before startup doesnt reach 8
hours, it will report this error.
Possible reason——
Troubleshooting:
The complete unit shall be preheated for more than 8 hours before startup.
2.2.4.132 U2 ODU capacity DIP switch/jumper cap setting error
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
ODU mainboard detects that the capacity code doesnt comply with the actual unit capacity, or ODU
mainboard detects that the jumper cap value doesnt comply with the actual unit
Possible reason
Capacity DIP switch is wrong or jumper cap is wrong (for those models without jumper cap, it wont
be detected)
DIP switch or jumper cap is broken
Detecting circuit is abnormal
Troubleshooting:
2.2.4.133 U3 Power phase sequence protection
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
If phase loss or reverse of three-phase power is detected (e.g. incorrect connection of power supply