GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
234
2.2.4.140 UE auto charging of refrigerant is invalid
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
When outdoor ambient temperature exceeds the temperature range of auto charging of refrigerant
(normal temperature range is 0~40
°C
), the unit will report this error.
Possible reason——
Troubleshooting:
Cancel auto charging of refrigerant and change to manual charging of refrigerant.
2.2.4.141 Poor cooling and heating performances
Error judgment condition and method:
1. When electronic expansion valve is opened to 2000PLS in cooling operation of IDU and IDU coil
outlet pipe temperature is 5
°C
higher than inlet pipe temperature;
2. When electronic expansion valve is opened to 2PLS in heating operation of IDU and IDU coil
outlet pipe temperature is 12
°C
lower than saturated temperature corresponding to high
pressure;
Possible reason:
ODU cut-off valve is opened to the max flow without following the requirement.
System pipeline is blocked.
Operation environment exceeds the range.
Flow organization design is not good.
Refrigerant charging amount is insufficient.