EasyManuals Logo

Gree GMV5E Series User Manual

Gree GMV5E Series
308 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #266 background imageLoading...
Page #266 background image
GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
262
Step 10: Install a new oil separator.
If the original oil separator contains impurities inside, replace it.
Step 11: Install a new compressor.
Note:
Keep wiring identical to factory installation. Control varies with compressors. Wrong wiring or
inverse connection of the compressors may cause damage to units.
Cautions on replacement of compressors:
Before installing new compressors, remove the sealing rubbers and weld the compressors with
corresponding pipes. During welding, charge nitrogen into the pipes. Since compressors’ suction
and discharge pipes are made of copper plated steels, you need to prepare special welding rods
(containing 5% or more silver). Welding clearance should be controlled within 0.1~0.3mm,

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV5E Series and is the answer not in the manual?

Gree GMV5E Series Specifications

General IconGeneral
BrandGree
ModelGMV5E Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals