GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
47
Manifold at indoor unit side
Manifold at indoor unit side can be selected as per total capacity of downstream indoor unit(s). Refer
to the following table.
Outdoor unit 1 Outdoor unit 2 Outdoor unit 3
indoor manifold
R410A Refrigerant System
Total capacity of downstream indoor unit(s) C (kW)
Model
Y-type Manifold
C<20.0
FQ01A/A
20.0≤C≤30.0
FQ01B/A
30.0<C≤70.0
FQ02/A
70.0<C≤135.0
FQ03/A
135.0<C
FQ04/A
T- type Manifold
C≤40.0
FQ14/H1
C≤68.0
FQ18/H1
68.0<C
FQ18/H2