MAINTENANCE
C5 Indoor capacity switch error
De-energize the unit and then, energize it
again. If the malfunction is removed, the
code will be cleared.
E6
Communication
malfunction(between outdoor
and indoor mainboard)
The communication line of the unit is
not connected.
The communication line is not through.
The communication line of the unit is
not connected correctly.
The two ends of communication line
are not mounted with magnetic ring.
The outdoor unit is not electrically
powered
It will be cleared once communication
recovers or it will be shown all the time.
E6
Communication
malfunction(between outdoor
mainboard and wired controller)
The communication line of the unit is
not connected.
The communication line is not through.
The communication line of the unit is
not connected correctly.
The two ends of communication line
are not mounted with magnetic ring.
The outdoor unit is not electrically
powered
It will be cleared once communication
recovers or it will be shown all the time
Fc High pressure sensor error
The sensor is damaged.
The wire of the sensor is loose.
The position of the sensor is wrong
It will be automatically cleared after the
failure is removed.
F9
Heat exchanger-leaving water
temperature sensor error
The plug on temperature sensor is
not correctly connected to the socket on
mainboard.
The resistance of temperature sensor
is not correct.
It will be automatically cleared after the
failure is removed.
dH
Heat exchanger-leaving water
temperature sensor error
The plug on temperature sensor is
not correctly connected to the socket on
mainboard.
The resistance of temperature sensor
is not correct.
It will be automatically cleared after the
failure is removed.
F1
Refrigerant liquid line temperature
sensor error
The plug on temperature sensor is
not correctly connected to the socket on
mainboard.
The resistance of temperature sensor
is not correct.
It will be automatically cleared after the
failure is removed.
F8
Heat exchanger-entering water
temperature sensor error
The plug on temperature sensor is
not correctly connected to the socket on
mainboard.
The resistance of temperature sensor
is not correct.
It will be automatically cleared after the
failure is removed.
FE
Water tank water temperature
sensor 1 error
The plug on temperature sensor is
not correctly connected to the socket on
mainboard.
The resistance of temperature sensor
is not correct.
It will be automatically cleared after the
failure is removed.
FL
Water tank water temperature
sensor 2 error
The plug on temperature sensor is
not correctly connected to the socket on
mainboard.
The resistance of temperature sensor
is not correct.
It will be automatically cleared after the
failure is removed.