No AC Connection No Utility
Please confirm grid is lost or not.
Check the grid connection is good or not.
Check the switches on the cable are on or not.
Output High DCI
Output DC current too high.
Please refer to the local grid
standard for disconnection time
when the output DC current is
too high.
Restart inverter.
Please contact Growatt service center if restart can’t
solve the problem.
Bat Voltage High Battery Voltage higher than 60V
Check the voltage of battery is in the range of
specification or not.
Check the battery connection is right or not
If battery is really higher than 60V. Please disconnect
the connection of battery and check inverter.
Bat Voltage Low Battery Voltage Lower than 42 V
Check the real voltage of battery.
Check the wire of battery and inverter is good or
not.
BMS Warning:XXX BMS report warning
Check the warning information from lithium battery
user manual.
Please contact Growatt service center if restart can’t
solve the problem.
BMS error:XXX BMS report error
Check the warning information from lithium battery
user manual.
Please contact Growatt service center if restart can’t
solve the problem.
EPS Volt Low EPS output voltage low
Check the load of EPS. If overload occurred, reduce
load.
Restart inverter again.
Error Message
Error Message Description Suggestion
Error 411 Internal communication failed
Restart inverter.
Please contact Growatt service center if restart can’t
solve the problem.
Error 417 Sample fault
Restart inverter
Please contact Growatt service center if restart can’t
solve the problem
Error 418
DSP and COM firmware version
unmatch, system fault.
Read DSP and COM firmware version from LCD or
shinebus.
Check if the firmware is correct.
Error 303
Inverter L N reversed or ground
failed
Check the L line and N line is reversed or not.
Check the PE s connected well or not.

Other manuals for Growatt SPH6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Growatt SPH6000 and is the answer not in the manual?

Growatt SPH6000 Specifications

General IconGeneral
ModelSPH6000
CategoryInverter
Rated Power6000 W
Max. DC Voltage550 V
Max. Output Current27.3 A
Start Voltage150 V
Nominal DC Voltage360V
Number of DC Inputs2
Number of MPP Trackers2
Nominal AC Power6000 W
Max. AC Power6600 W
Nominal Grid Frequency50 Hz / 60 Hz
Total Harmonic Distortion<3%
DC SwitchYes
Protection ClassIP65
Operating Temperature Range-25°C to +60°C
Max. Output Power6600 W
Output Voltage230V
Output Frequency50/60 Hz
Nominal AC Voltage230V
AC Voltage Range180V-280V
Power Factor0.8 leading - 0.8 lagging
CommunicationRS485
Cooling MethodNatural Convection

Related product manuals