INSTALLATION - WATER TRANSFER:
Using 2 Float switch (one float in UG tank, one float in OH tank)
Start condition:
If water level in UG tank is high ie. Float A is up and water level in OH tank is
low ie. Float B is down, panel will start pump A. Panel will alternate between
pump A and pump B, after previous cycle is completed. LCD screen will display
pump A/B run on screen.
Stop condition:
If the water level in UG tank is low ie. Float A is down, if any of the pump(s) are
running, panel will stop the pump(s) indicating that there is not enough water
in UG tank. LCD screen will display No water.
If the water level in OH tank is high ie. Float A is up. Panel will stop the pump(s)
that are running indicating that the OH tank is full. LCD screen will display Full.
On any of the situation stated above occur, pump(s) will stop running.