9.1.1 Multipump system operating indications
When connecting Grundfos GO Remote to a multipump setup
and choosing "system view", Grundfos GO Remote will indicate
the system's operating status and not the status of the pump
itself. Therefore the indicator light in Grundfos GO Remote might
differ from the indicator light shown on the pump's operating
panel. See the table below.
9.2 Resetting a fault indication
To reset a fault indication, eliminate the fault cause, see section
9.4 Fault finding table, and reset the pump by pressing the button
on the pump. If the pump does not revert to normal duty, the fault
cause is not eliminated.
If the fault disappears by itself, the fault indication is automatically
reset.
A fault can also be reset by using Grundfos GO Remote. See
section 9.3 Reading out warning and alarm codes in Grundfos
GO Remote.
9.3 Reading out warning and alarm codes in Grundfos
GO Remote
To read out alarm codes and text, connect the pump to Grundfos
GO Remote and navigate to the "Alarms and warnings" menu.
Grundfos Eye in the dashboard indicates the warning or alarm.
An overview of warnings and alarms is also available in section
9.4 Fault finding table.
For instructions on how to connect the pump to Grundfos GO, see
section 8.3 Connecting the pump to Grundfos GO Remote.
Grundfos Eye,
master pump
Grundfos Eye,
slave pump
Grundfos Eye,
Grundfos GO
Remote
Green Green Green
Green or yellow Yellow or red Yellow
Yellow or red Green or yellow Yellow
Red Red Red
CAUTION
Pressurised system
Minor or moderate personal injury
- Before dismantling the pump, drain the system or
close the isolating valve on either side of the
pump. The pumped liquid may be scalding hot and
under high pressure.
WARNING
Electric shock
Death or serious personal injury
- Switch off the power supply for at least 3 minutes
before you start any work on the product. Lock the
main switch in position 0. Type and requirements
as specified in EN 60204-1, 5.3.2.
WARNING
Electric shock
Death or serious personal injury
- Make sure that other pumps or sources do not
force flow through the pump even if the pump is
stopped.
If the power cable is damaged, it must be replaced
by the manufacturer, the manufacturer's service
partner or a similarly qualified person.
Step Action Illustration
1
A. Select the
"Alarms and
warnings" menu
from the
dashboard,
B. You can also
reach the menu by
tapping Grundfos
Eye.
Dashboard_With_Alarm
2
The "Alarms and
warnings" menu
shows the current
alarm code and
text. A log history
of previous alarms
and warnings is
also available.
When the fault is
corrected, reset
the alarm by
pressing the
"Reset alarm"
button.
Alarm_Warning
When connecting Grundfos GO to one of the pumps
of a twin-head pump, Grundfos GO reads out alarm
codes and texts for that pump. If you want to see
alarms and warnings for the other pump, connect to
this instead.