5. First start-up
Do not start the pump until the system has been filled with liquid
and vented. Furthermore, the required minimum inlet pressure
must be available at the pump inlet. See section 12. Technical
data.
The system cannot be vented through the pump. The pump is
self-venting.
Caution
The discharge valve must be opened immediately
after start-up of the pump. Otherwise the
temperature of the pumped liquid may become
too high and cause damage to the equipment.
Step Action Illustration
1
Switch on the power supply to the pump.
Note: When switched on, the pump will start after approx.
5 seconds.
TM05 5550 3812
2 Control panel at first start-up.
TM05 5551 3812
3
The pump has been factory-set to the intermediate
proportional-pressure curve.
Select the control mode according to the system
application.
TM05 5551 3812

Other manuals for Grundfos MAGNA1 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grundfos MAGNA1 Series and is the answer not in the manual?

Grundfos MAGNA1 Series Specifications

General IconGeneral
Insulation ClassF
TypeCirculator pump
Control Panel PositionIntegrated
SeriesMAGNA1
WeightVaries by model
Power Supply3 x 380-480 V, 50/60 Hz
Pump HousingCast iron
Connection TypeFlanged
Voltage380-480 V
MaterialCast iron, stainless steel
Temperature Range-10°C to +110°C
Ambient Temperature Range0°C to +40°C