PHP A-1 Instruction Manual / Operation and display
21
DISPLAY LEVEL... (2) MAKEUP:
Current vessel level and operating mode
of makeup (“On”, “Off”, “locked_s” or
“1x_min”). At operating modes “locked”
and “1x (one-time)” the number in
brackets shows the remaining time in
seconds resp. in minutes.
Entire makeup amount up to now
Level L/state
Prev. overall
amount
Rem. amount/
rem. time
Softening cartridge
rem. capacity
Available amount since the last
reset of the amount not displayed in
operating mode “time-controlled”
Display shows the remaining amount
within the displayed remaining time.
Not displayed in operating mode
“amount-controlled”
Display shows the remaining
capacity of the softener cartridge.
Only displayed if “softening MWE”
was activated in menu “settings”
Display shows the remaining
capacity of the desalination cartridge.
Only displayed if “desalination MVE”
was activated in menu “settings”
Current operating mode of the
makeup acc. to menu “settings”
(“amount-controlled”, “time-
controlled” and “uncontrolled”)
Menu item is displayed only if “degassing”
was activated in menu “settings”
Display shows the current operating
stage of the degassing (“Off”,
“locked (reason)”, “pressure build-
up”, “degassing fast/normal”, “break
fast/normal”) and the remaining time
of the respective operation stage
... Off
degassing disabled
... locked
degassing is locked due to too
high temperatures (T1 or T2) or
too high pressure (P)
... pressure build-up
pump builds up the necessary
pressure for degassing
... degassing (fast)
fast degassing active
... break (fast)
shortened break because fast
degassing is active
... degassing (normal)
degassing cycle is active
... break (normal)
normal break because fast
degassing is not active
remaining time of the fast degassing
(after this normal degassing) only
displayed if “fast degassing” is active
Rem. amount
Desalination
cartridge
rem. capacity
Operating mode
Display level... (2)
degassing
Current operat.
stage
Fast degassing
rem. time
DISPLAY LEVEL... (2) PRESSURE MAINTENANCE:
Press. P1/Level L
Current plant pressure and vessel
level, lower and upper working
pressure setpoint
Current operating mode of
pump 1 (“On” or “Off”) and elapsed
hour counter for the entire run-time
of the pump 1
Current operating mode of pump
2 (“On” or “Off”) and elapsed hour
counter for the entire run-time of the
pump 2 only displayed at systems
PHP Duo
Current temperature in the overflow
pipe inside the device
Current level in vessel 1 first at
modular only displayed if level
measurement L2 was activated in
menu “settings”
Current level in vessel 2 (additional
at EMCM) only displayed if level
measurement L2 was activated in
menu “settings”
Current operating mode of the
pumps acc. to menu “settings” only
displayed at systems Duo and Maxi
Current priority pump - the pump
which starts at first if the lower
working pressure is underrun only
displayed at systems PHP Duo
Operating mode of the level
measurement acc. to menu
“settings” only displayed if level
measurement L2 was activated in
menu “settings”
Operation pump 1
Operation pump 2
Sensor T1
Level L1
Level L2
Operating mode
pumps
Curr. priority pump
Operating mode
level