Connection terminals for the mains supply
Phases Terminals
Single-phase N, PE, L
Three-phase L1, L2, L3, PE
Connection terminals for inputs and outputs
DANGER
Electric shock
Death or serious personal injury
Make sure that the wires to be connected to the connection groups below are separated from each other by reinforced insulation
in their entire lengths.
B
Y
6
5
2
4
10
A
GENIbus A
GENIbus B
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
+24 V*
OC
DI
GND
+
+
+24 V*/5 V*
TM053511
Terminal Type Function
10 DI3/OC1
Digital input/output, configurable.
Open collector: Maximum 24 V resistive or inductive.
4 AI1
Analog input:
0.5 - 3.5 V, 0-5 V or 0-10 V.
2 DI1
Digital input, configurable.
Digital input 1 is factory-set to be start or stop input where an open circuit results in stop. A jumper has
been factory-fitted between terminals 2 and 6. Remove the jumper if digital input 1 is to be used as
external start or stop or any other external function.
5 +5 V Power supply to a potentiometer or sensor.
6 GND Protective earth.
A GENIbus, A GENIbus, A (+).
Y GENIbus, Y GENIbus, Y (GND).
B GENIbus, B GENIbus, B (-).
Related information
4.2.4 Connecting an external switch
4.2.7.2 Standard functional module, FM 200
Inputs and outputs
The module has these connections:
two analog inputs
two digital inputs or one digital input and one open-collector output
Grundfos Digital Sensor input and output
two signal relay outputs
GENIbus connection.
The inputs and outputs are internally separated from the mains-conducting parts by reinforced insulation and galvanically separated from other
circuits. All control terminals are supplied with protective extra-low voltage (PELV), ensuring protection against electric shock.
Signal relay 1
LIVE: You can connect supply voltages up to 250 VAC to the output.
PELV: The output is galvanically separated from other circuits. Therefore, you can connect the supply voltage or protective extra-low voltage to
the output as desired.
Signal relay 2
PELV: The output is galvanically separated from other circuits. Therefore, you can connect the supply voltage or protective extra-low voltage to
the output as desired.