EasyManua.ls Logo

Grundfos RADIOMODULE 2G4 - Priority of Settings

Grundfos RADIOMODULE 2G4
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6. Press the Right button to continue.
7. Select Wired GENIbus as the communication method to be used between the two motors.
8. Press the Right button twice to continue.
9. Select the desired multimotor function. See Multipump or multimotor function.
10. Press the Right button to continue.
11. Press OK to search for other motors.
12. Select the additional motor from the list.
13. Press the Right button to continue.
14. Set Time for pump changeover.
This is the time at which the alternation between the two motors is to take place.
This step applies only if you have selected Alternating operation, time and if the motors are fitted with FM 300.
15. Press the Right button to continue.
16. Press OK to confirm the setting.
The multipump or multimotor function icons appear at the bottom of the operating panels.
6.46.5 Disabling a multipump or multimotor system with Grundfos GO Remote
1. Go to Assist.
2. Select Multi-pump setup and press Disable.
3. Press the Right button to continue.
4. Confirm the setting by pressing Send.
5. Press Finish.
6.46.6
Disabling a multipump or multimotor system with the advanced operating panel
1. Go to Assist.
2. Select Setup of multi-pump system.
3. Press the Right button to continue.
4. Press OK to confirm No multi-pump function.
5. Press the Right button to continue.
6. Press OK to confirm.
6.47 "Description of control mode"
The function is only available in the advanced operating panel.
The function describes each of the control modes available for the product.
Related information
6.5 "Control mode"
6.48 "Assisted fault advice"
This function provides guidance and corrective actions in the event of product failure.
6.49
Priority of settings
With Grundfos GO Remote, you can set the motor to operate at maximum speed or to stop.
If two or more functions are enabled at the same time, the motor operates according to the function with the highest priority.
If you have set the motor to maximum speed via the digital input, the motor operating panel or Grundfos GO Remote can only set the motor
to Manual or Stop.
The priority of the settings appears from the table below:
Priority
Start/stop
button
Grundfos GO Remote or operating panel on
motor
Digital input Bus communication
1 Stop
2
Stop
*
3 Manual
4
Maximum speed / User-defined speed
*
5 Stop
6 User-defined speed
7 Stop
60
English (GB)

Table of Contents

Related product manuals