Functional module
Signal relay
(Terminals 12, GND)
FM 100 (basic) -
FM 200 (standard) -
FM 300 (advanced) •
Functions
You can configure the signal relays to be activated when the product changes to one of the following states:
• Not active
The relay has been deactivated.
• Ready
The motor may be running or is ready to run, and no alarms are active.
• Alarm
There is an active alarm, and the motor is stopped.
• Operating (Operation)
Operating equals Running, but the motor is still in operation when it is stopped, for example, by the Stop function or "Limit exceeded".
• Running (Pump running)
The motor shaft is rotating.
• Warning
There is an active warning.
• Limit 1 exceeded
When you have set this function and the limit is exceeded, the signal relay is activated.
• Limit 2 exceeded
When you have set this function and the limit is exceeded, the signal relay is activated.
• External fan control (Control of external fan).
When you select this function, the relay is activated if the internal temperature of the motor electronics reaches a preset limit value. In this
way the relay activates external cooling to add additional cooling to the motor.
• Digital input 1,state
Follow digital input 1. If digital input 1 is triggered, digital output is also triggered.
• Digital input 2,state
Follow digital input 2. If digital input 2 is triggered, digital output is also triggered.
• Digital input 3,state
Follow digital input 3. If digital input 3 is triggered, digital output is also triggered.
• Digital input 4,state
Follow digital input 4. If digital input 4 is triggered, digital output is also triggered.
Related information
2.7 Identification of the functional module
6.8 "Digital inputs"
6.8.1 Timer function for a digital input
6.9 "Digital inputs/outputs"
6.11 "Analog output"
The inputs and outputs available depend on the functional module fitted in the motor.
Functional module
Analog output
(Terminals 12, GND)
FM 100 (basic) -
FM 200 (standard) -
FM 300 (advanced) •
The analog output enables external control systems to read specific operating data.
To set the analog output, make these settings.
Output signal
Possible signal types:
• 0-10 V
• 0-20 mA
• 4-20 mA.