2. Remove the CIM (Communication Interface Module) cover (C1) by pressing the locking tab (D) and lifting the end of the cover (C2). Then
lift the cover off the hooks (C3).
D
C2
C3
C1
TM069905
3. Remove the screw (E).
E
TM069906
4. Fit the module by aligning it with the three plastic holders (F) and the connection plug (G). Press the module home, using your fingers.
F
G
TM069907
5. Fit and tighten the screw (E) to 1.3 Nm.
6. Make the electrical connections to the module as described in the instructions supplied with the module.
7. Connect the cable screens of the bus cables to protective earth via one of the earth clamps (H).
H
TM069908