English (GB)
34
Measured parameter
Select one of the parameters, i.e. the parameter to be measured
in the system by the sensor connected to the actual analog input.
See fig. 55.
Fig. 55 Overview of sensor locations
Unit
Available measuring units:
Electrical signal
Select signal type:
• 0.5 - 3.5 V
•0-5 V
• 0-10 V
• 0-20 mA
• 4-20 mA
Sensor range, min. value
Set the minimum value of the connected sensor.
Sensor range, max. value
Set the maximum value of the connected sensor.
Factory setting
See section 31. Factory settings.
14.9 Built-in Grundfos sensor
You can select the function of the built-in sensor in the "Built-in
Grundfos sensor" menu.
Set the "Built-in Grundfos sensor" via the "Assisted pump setup"
menu. See section 14.44 Assisted pump setup.
If you perform the setting manually in the advanced control panel,
you must enter the "Analog inputs" menu under the "Settings"
menu in order to access the "Built-in Grundfos sensor" menu.
If you perform the setting manually via Grundfos GO, you need to
enter the menu for the "Built-in Grundfos sensor" under the
"Settings" menu.
Function
You can set the built-in sensor to these functions:
• Grundfos diff.-pressure sensor
- Not active
- Feedback sensor
- Setpoint influence
- Other function.
• Grundfos temperature sensor
- Not active
- Feedback sensor
- Setpoint influence
- Other function.
Factory setting
See section 31. Factory settings.
TM06 2328 3914
Sensor function/measured parameter Pos.
Inlet pressure 1
Diff. press., inlet 2
Liquid temperature 3
Diff. press.,outlet 4
Diff. press.,pump 5
Operating mode 6
Press. 2, external 7
Diff. press., ext. 8
Storage tank level 9
Feed tank level 10
Pump flow 11
Flow, external 12
Liquid temperature 13
Temperature 1 14
Temperature 2 15
Date and time 16
Ambient temp. Not shown
Other parameter Not shown
Parameter Possible measuring units
Pressure bar, m, kPa, psi, ft
Level m, ft, in
Flow rate m
3
/h, l/s, yd
3
/h, gpm
Liquid temperature °C, °F
Other parameter %
PT PT PT
PT
TT
TT
TT
Q
Q
DPT
DPT DPT
LT LT
DPT DTT
1
5
24
910
7
12
816 15
313 6 14
11
Pump variant Built-in Grundfos sensor
TPE3, TPE3 D
TPE2, TPE2 D -