EasyManua.ls Logo

Grundfos TPE 2 Series - Factory Settings

Grundfos TPE 2 Series
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English (GB)
64
31. Factory settings
*)
Only available if you have fitted an advanced functional module, FM 300.
Function is enabled.
Function is disabled.
- Function is not available.
Settings TPE3, TPE3 D TPE2, TPE2 D
Function
description on
page
Setpoint Auto 27
Operating mode Normal Normal 27
Control mode AUTO
ADAPT
Const. curve 28
Date and time
*)
*)
FLOWLIMIT
-
Automatic Night Setback
-
Temperature influence
-
Buttons on product 45
Controller (Controller settings) 38
Ti 1.0 0.5
Kp 8.0 0.5
Operating range 39
Min. 25 % 25 %
Max. 100 % 100 %
Ramps -
44
Ramp-up 1 second 1 second
Ramp-down 3 seconds 3 seconds
Number (Pump number) 1 1 44
Radio communication 45
Analog input 1
❍❍
33Analog input 2
❍❍
Analog input 3
❍❍
Built-in Grundfos sensor -
34
Grundfos differential pressure sensor Feedback sensor -
Grundfos temperature sensor
-
Pt100/1000 input 1
❍❍
35
Pt100/1000 input 2
❍❍
Digital input 1
❍❍
35
Digital input 2
❍❍
Digital in/output 3
❍❍
36
Digital in/output 4
❍❍
Pulse flowmeter
❍❍
43
Predefined setpoints
❍❍
42
Analog output
❍❍
37
External setpoint function
❍❍
39
Signal relay 1
❍❍
36
Signal relay 2
❍❍
Limit 1 exceeded -
43
Limit 2 exceeded -
Standstill heating
❍❍
44
Motor bearing monitoring
❍❍
44
Pump name Grundfos Grundfos 46
Connection code - - 46
Unit configuration SI SI 45

Table of Contents

Related product manuals