9.4.2 Connection terminals, standard functional module
(FM 200)
The standard module has these connections:
two analog inputs
two digital inputs or one digital input and one open-collector
output
Grundfos Digital Sensor input and output
two signal relay outputs
GENIbus connection.
See fig. 22.
Inputs and outputs
All inputs and outputs are internally separated from the power
supply-conducting parts by reinforced insulation and
galvanically separated from other circuits.
All control terminals are supplied by safety extra-low voltage
(SELV), thus ensuring protection against electric shock.
Signal relay outputs
– Signal relay 1:
LIVE:
Power supply voltages up to 250 VAC can be connected to
this output.
SELV:
The output is galvanically separated from other circuits.
Therefore, the supply voltage or safety extra-low voltage
can be connected to the output as desired.
– Signal relay 2:
SELV:
The output is galvanically separated from other circuits.
Therefore, the supply voltage or safety extra-low voltage
can be connected to the output as desired.
Power supply (terminals N, PE, L or L1, L2, L3, PE).
A galvanically safe separation must fulfil the requirements for
reinforced insulation including creepage distances and
clearances specified in EN 61800-5-1.
Note
Note
Digital input 1 is factory-set to be start/stop input
where open circuit will result in stop.
A jumper has been factory-fitted between
terminals 2 and 6. Remove the jumper if digital
input 1 is to be used as external start/stop or any
other external function.
Note
Note
As a precaution, the wires to be connected to the
connection groups below must be separated
from each other by reinforced insulation in their
entire lengths.