DA98A AC Servo Drive Unit
User Manual
38
7
Drive stop
abnormal
Input terminals of
CCW, CW drive stop
are both broken off.
Check the
connection and the
power supply of the
input terminals.
8
The position
deviator overflow
Motor is
mechanically
locked.
Input instruction
pulse is abnormal.
Check
mechanical part
of the load.
Check the
instruction pulse.
Check whether
the motor runs by
instruction pulse.
Encoder connection
is wrong.
Check the
connection.
Encoder is damaged. Change the motor.
Encoder cable is
inferior.
Change the cable.
9 Encoder fault
Encoder cable is too
long to cause the
encoder voltage too
low.
Shorten the
cable.
Use multi-core
parallel power
supply.
15V internal voltage
of input control is
low.
Check the control
power supply.
10
Control power
supply
undervoltage
Internal connector
assembly of drive
unit is inferior.
Switch power supply
is abnormal.
Chip is damaged.
Change the AC
servo drive unit.
Check the
connector
assembly.
Check the switch
power supply.
Occuring as control
power supply is
powered on
Circuit board is at fault.
Change the AC
servo drive unit.
Power voltage is
low.
Overheated.
Check the AC
servo drive unit.
Power on again.
Change the AC
servo drive unit.
U, V, W of drive unit
are short circuit.
Check the
connection.
Grounding is not good.
Be grounded
correctly.
Motor insulation is
damaged.
Change the motor.
11 IPM module fault
Occuring as motor is
running
It is interfered.
Increase the
circuit filter.
Be far away from
the interference
source.