EasyManua.ls Logo

GST GST200-2 - Operator Functions

GST GST200-2
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GST200-2 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 31
Fig. 6-8
Sum:32 // Total number of keys on ZCP
N01: L02N001 Sounder // Key No. 1 is defined as a sounder of Loop 2
whose address is 001.
N02: Zone 01 //Key No. 2 is defined as Zone 1 indicator
N03: L01N004 Sounder //Key No. 3 is defined as a sounder of Loop 1
whose address is 004.
Entering No. 7 to choose “7: Browsing C&E” will enter the screen for browsing C&E
equation, as shown in Fig. 6-9.
Fig. 6-9
The part before “=” is the condition and that after it is the result.
“×” means “and”, and “+” means “or”.
A condition is composed of the following items:
General Condition: A device can be activated if its zone number, code and device
type are correct.
Special Condition: Both zone number and device type can be defined. If events
with the same zone number and device type reach a defined number, this special
condition comes into effect. Asterisk wildcard “*” represents any number used in
ENTER
Browse C&E
Sum: 003
C&E 001
C&E 002
C&E 003
Browse C&E
C&E 001
G0100103 × G0100203+G0100203 ×
G0100303 + G0100103 × G0100303 +
G0100103 × G0100203 × G0100303 =
G0100413 00
G(S) 01 001 03
Device type
Device address/Quantity of events defined in special condition
Zone number of the device
G: General conditions S: Special conditions
Browse
Sum:32
N01: L02N001 Sounder
N02: Zone 01
N03: L01N004 Sounder

Table of Contents

GST GST200-2 - Operator Functions