www.gtec-power.de 53
6. Product Specifications
This chapter provides the specifications of the product, including environment characteristics
mechanical characteristics and electrical characteristics.
6.1 Applicable Standards
The UPS has been designed to conform to the following European and international standards:
Table 6-1
Item
Normative reference
General safety requirements for UPS used in operator access areas
IEC62040-1-1 EN62040-1
Electromagnetic compatibility (EMC) requirements for UPS
IEC62040-2
IEC-EN62040-2 (2018)
Method of specifying the performance and test requirements of
UPS
IEC62040-3
Note
The above mentioned product standards incorporate relevant compliance clauses with generic IEC
and EN standards for safety (IEC/EN/AS60950 and IEC/EN 62477-1), electromagnetic emission and
immunity (IEC/EN61000 series) and construction (IEC/EN60146 series and 60950 and 62477-1).
6.2 Environmental Characteristics
Table 6-2
Item
Unit
Parameter
Acoustic noise level
at 1 meter
dB
58dB @ 100% load, 55dB @ 45% load
Altitude of Operation
m
≤1000, load de-rated 1% per 100m from 1000m to 2000m
Relative Humidity
%
0-95, non-condensing
Operating Temperature
10 and 15 KVA: 0-40°C
20-30-40 KVA at PF=1: 0-30°C
20-30-40 KVA at PF=0,9: 0-40°C
warning for battery is recommended 15-25°C, due battery life
is halved for every 10°C increase above 20°C
UPS Storage
Temperature
-40 ~ +70, warning battery life is halved for every 10°C
increase above 20°C