www.gtec-power.de 55
6.4.2 Electrical Characteristics Battery
Table 6-5
Quantity of lead-acid
cells
40 batteries 12V, 240 cells 2V
2,25V/cell (selectable from 2,2V/cell
~
2,35V/cell)
Constant current and constant voltage charge mode
2,35V/cell (selectable from: 2,30V/cell~2,45V/cell)
Constant current and constant voltage charge mode
Temperature
compensation (option)
Final
discharging voltage
1,65V/cell (selectable from: 1,60V/cell~1,75V/cell)
@0,6C discharge current
1,75V/cell (selectable from: 1,65V/cell~1,8V/cell)
@0,15C discharge current
(EOD voltage changes linearly within the set range
according to discharge current)
Note
When the battery in use is different than the default 40 (range 32-44), ensure the actual number and
the set number is the same, otherwise batteries may be damaged.
6.4.3 Electrical Characteristics Inverter Output
Table 6-6
220/230/240 (Line-N), std=230
±1,5% (0-100% linear load)
50/60±0,1% (battery mode)
default
±
3Hz, Settable
±
0.5Hz
~±
5Hz
default 2Hz/s, settable, 0,5
~
3
10-40kVA <1% (linear load)
10-15K <5,5% (non-linear load),
20+30+40kVA <6% (non-linear load)
according t IEC/EN62040-3
<110% 60min; 110%~125%,10min;
125%~150%,1min
(note 1) 20-30-40KVA model has Dynamic PF, it is PF=1 up to 30°C, over 30°C is 0,9