51
Initial Setting Examples Section 3-1
Example 3 (Models with Position-proportional Control)
5
45
flot
clos
Input type: 5 (K thermocouple,
−200.0°C to 1,300.0°C)
Control method: Floating control (default)
Travel time: 45 s
Setup Procedure
Power ON
Initial Setting Level
Set input
specifications
Set control
specifications
Start operation
Power ON
PV/SP
Press the O Key for
at least 3 s.
Press the O Key for
at least 1 s.
Press the O Key twice
(for less than 1 s).
Start operation.
Set travel time
Check input type. Input Type:
Check that control
method is floating
control.
Floating
control:
Close
control:
Use the
U and D
Keys to set the
travel time to 45.
Travel time:
25.0
0.0
M
M
M
mot
45
in-t
5
clfl
flo t
25.0
0
c
c
50.0
100.0
0.20
0.40
0.20
d.prg
0
M
s-no
4
M
0
M
d. seg
M
sp
50.0
c
0.00
M
time
M
end
d. seg
MM
25.0
50.0
ru n
r-r
c
0
50. 0
0. 00
1 2 3
100. 0 100. 0 50. 0
0. 20 0. 40 0.20
4
0
Set point
Segment 1
Segment 2
Segment 3
Time (h.min)
Parameter
Setting
Number of Segments Used (Program 0)
Program No.
Segment No.
Segment Set Point
Segment Time (h.min)
Operation Level
PV/SP
Operation Level
Operation Level
Initial Setting Level
Make sure that
the Display
Program
Selection is 0.
Display Program
Selection
Use the
UD
Keys to set the
Number of
Segments Used.
No. of Segments
Used changed
from 8 to 4.
Use the
UD
Keys to set the
Display Segment
Selection.
Display Segment
Selection changed
from end to 0.
Segment Set
Point changed
from 0.0 to 50.0.
Use the
UD
Keys to set the
Segment Set
Point.
Use the
UD
Keys to set the
Segment Time.
Set segments 1,
2, and 3 in the
same way.
Segment Time
The default is
h.min.
Display Segment
Selection
end will be
displayed when
all segments are
set.
Run/Reset
changed from rst
to run.
Confirm that the set
point is 50.0°C.
Set Run/Reset to
Run.
PV/SP
Program Setting Level
Program Setting
Level
Set the programs
Press the O Key three times
(for less than 1 s).