7
Pre-installation checklist
Table 4 Checklist before installation
Item Requirements Result
Installation
site
Ventilation
There is a minimum clearance of 100 mm (3.94 in)
around the inlet and outlet air vents for heat
dissipation of the firewall chassis.
A good ventilation system is available at the
installation site.
Temperature
Operating:
{ Without hard disks: 0°C to 45°C (32°F to 113°F)
{ With hard disks: 5°C to 40°C (41°F to 104°F)
Storage: –40°C to +70°C (–40°F to +158°F)
Relative humidity
Operating:
{ Without hard disks: 5% RH to 95% RH,
noncondensing
{ With hard disks: 10% RH to 90% RH,
noncondensing
Storage: 5% RH to 95% RH, noncondensing
Cleanness
Dust concentration 3 × 10
4
particles/m
3
No dust on desk within three days
ESD prevention
The equipment, workbench, and rack are reliably
grounded.
The equipment room is dust-proof.
The humidity and temperature are at an acceptable
level.
Wear an ESD wrist strap and make sure it makes
good skin contact and is reliably grounded when
installing FRUs.
Put the removed interface modules away on an ESD
workbench, with the PCB upward, or put them in ESD
bags for future use.
Touch only the edges, instead of electronic
components when observing or moving a removed
interface module.
EMI prevention
Take effective measures to protect the power system
from the power grid system.
Separate the protection ground of the firewall from
the grounding device or lightning protection
grounding device as far as possible.
Keep the firewall far away from radio stations, radar
and high-frequency devices working in high current.
Use electromagnetic shielding when necessary.
Lightning
protection
The grounding cable of the chassis is reliably
grounded.
The grounding terminal of the AC power receptacle is
reliably grounded.
(Optional.) A power lightning arrester is installed.
Electricity safety
Equip a UPS.
Locate the power switch in the equipment room. In
case of emergency during operation, switch off the
power switch.

Table of Contents

Other manuals for H3C SecPath F1020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the H3C SecPath F1020 and is the answer not in the manual?

H3C SecPath F1020 Specifications

General IconGeneral
BrandH3C
ModelSecPath F1020
CategoryFirewall
LanguageEnglish

Related product manuals