14 Parameter Description
KRONOS 20 83
No. Name Signification
3198 SExceptionFlag
Level: 1
Range: 0000..FFFF Hex
Page(s):
Sentinel for the occurrence of Exeption error
3400 ClosedLpPowerActive
Level: 1
Range: 0..1
Page(s):
Operation mode Closed Loop with power feedback
active
3401 ClosedLpLambdaActive
Level: 1
Range: 0..1
Page(s):
Operation mode Closed Loop with lambda sensor feed-
back active
3402 ClosedLpCH4Active
Level: 1
Range: 0..1
Page(s):
Operation mode Closed Loop with CH4 sensor feed-
back active
3410 MixtureFlowRate
Level: 1
Range: 0..25000 m³n/h
Page(s):
Calculated mix flow
3411 CalculatedPower
Level: 1
Range: 0..2500 kW
Page(s):
Calculated generator power
3412 VolumetricEfficiency
Level: 1
Range: 0,5..1
Page(s):
Current value for volumetric Efficiency of the engine
3413 MechanicalEfficiency
Level: 1
Range: 0,1..0,5
Page(s):
Current value for mechanical Efficiency of the engine
3420 ThroatVelocity
Level: 1
Range: 0..200 m/s
Page(s):
Calculated gas velocity in the gas mixer throat
3421 ThroatDeltaPressure
Level: 1
Range: 0..30000 Pa
Page(s):
Calculated pressure difference in the gas mixer throat
3422 HolesDeltaPressure
Level: 1
Range: 0..30000 Pa
Page(s):
Calculated pressure difference in the gas holes of the
gas mixer