14 Parameter Description
84 KRONOS 20
No. Name Signification
3430 GasTotalDeltaPress
Level: 1
Range: 0..30000 Pa
Page(s):
Calculated overall pressure difference
3431 GasValveOpeningArea
Level: 1
Range: 0..65535 mm²
Page(s):
Calculated opening area of the E-LES
3440 ZPRDroopPressure
Level: 1
Range: 0..30000 Pa
Page(s):
Calculated pressure droop of the zero pressure regulator
3450 GasDensity
Level: 1
Range: 0,5..3 kg/m³
Page(s):
Current gas density (variation only at CH4 content
feedback)
3451 CalorificValue
Level: 1
Range: 5..100 MJ/m³
Page(s):
Current gas calorific value (variation only at CH4 con-
tent feedback)
3452 LambdaStoichiometric
Level: 1
Range: 1..30 m³/m³
Page(s):
Current gas lambda stoichiometric (variation only at
CH4 content feedback)
3453 GasFlowRateDesired
Level: 1
Range: 0..2500 m³n/h
Page(s):
Calculated gasflow setpoint based on lambda setpoint
(3462 LambdaDesiredValue)
3454 GasFlowRateActual
Level: 1
Range: 0..2500 m³n/h
Page(s):
Calculated gasflow rate based on output power feed-
back (2914 MeasuredPower)
3460 LambdaTempCorr
Level: 1
Range: -1,25..1,25
Page(s):
Current factor for temperature dependant lambda cor-
rection
3461 LambdaMap
Level: 1
Range: 0..2,5
Page(s):
Current value from lambda map
3462 LambdaDesiredValue
Level: 1
Range: 0..2,5
Page(s):
Temperature corrected actual lambda setpoint from
lambda map