Protocol description ASCII, SECS/HSMS
Customer manual
Version 1.2
LFM LP Reader 15.01.2019
Page 65 of 119
HERMOS AG
Gartenstrasse 19 Tel. +49(9279) 991-0
D-95490 Mistelgau Fax. +49(9279) 991-100
Locked page cannot be written
Check the page number to
be written, exchange the tag
for the new one
Maximum number of send
messages has been confirmed
(RS232 maxrepeat),
The terminal did not confirm
within the specified timeframe
Host system does not
acknowledge the message
Check availability oft he
host system,
Check RS232 cable and
connector, Ethernet cable
and connector,
Check IPAddress settings
A wrong transponder type
is used
(Read only or Read / Write
instead of multipage)
Check and replace
transponder type
Message too long or too short
or not received completely
Message too long or too short
or not received completely
Message length is longer
than indicated on the length
byte,
Check message length and
length byte
Message is longer than
specified in the length byte
Check message length,
check length byte
Not all characters are
transfered
(Intercharacter Timeout)
Check message syntax,
Check RS232 or Ethernet
connection
Unknown command was
received