EasyManuals Logo

Higen FDA7015 User Manual

Default Icon
147 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
3. Parameter setting
3-24
P06-04*
TRQ S-Mode
Unit
ms
Display range
0.0 ~ 2000.0
Manufactured
default
0.0
Torque control
If you adjust the S-mode operation time constant under the condition of satisfying the
operattion characteristics of the machine system, you can reduce the vibration and impact of the
machinery.
P06-05
In TRQ Range
Unit
%
Display range
0.0 ~ 100.0
Manufactured
default
10.0
Torque control
Torque
Actual torque
Set torque
reach range
Time [sec]
Time [sec]
OFF
ON
Set torque
reach completion
Torque
P06-06
Stop TRQ Range
Unit
%
Display range
0.0 ~ 100.0
Manufactured
default
10.0
Torque control
P06-07
10[V] TRQ
Unit
%
Display range
0 .0~ 300.0
Manufactured
default
100.0
Speed/Torque
control
This sets the command torque range applicable to the 10 [V] analog voltage in speed or
torque control mode of the servo drive.
P06-08
Auto Offset
Unit
-
Display range
ON / OFF
Manufactured
default
OFF
Speed/Torque
control
It automatically adjusts the offset voltage of the servo drive for analog 0[V] input of the host
controller.
P06-09
Manual Offset
Unit
mV
Setting range
-1000.0 ~ 1000.0
Manufactured
default
0.0
Speed/Torque
control

Other manuals for Higen FDA7015

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Higen FDA7015 and is the answer not in the manual?

Higen FDA7015 Specifications

General IconGeneral
BrandHigen
ModelFDA7015
CategoryServo Drives
LanguageEnglish

Related product manuals