(APPENDIX VII) CALIBRATION OF THE CONTROL UNIT | PAGE 109
Using the keys the voltage between phase and neutral measured by the con-
trol unit is adjusted to match the actual value.
* * * * MEASUREMENTS * * * *
Pressing the key completes the calibration process. The calibration process
can be interrupted by pressing the key
. Calibration of the system can be reset
by writing parameter 17 for the network voltage and parameter 18 for the genset
voltages.