(APPENDIX I) PARAMETERS TABLE | PAGE 57
Parameter PSW Description
Default
value
Range
22 2 Filtering of the ENT1 input. 1.0’ 0.0’’.. 120.0’
23 2 Filtering of the ENT2 input. 1.0’ 0.0’’.. 120.0’
24 2 Filtering of the ENT3 input. 1.0’ 0.0’’.. 120.0’
26 2 Dummy load power detection time. 5 ’’ 1’’..3000’
27 2 Load starting power detection time. 5 ’’ 1’’..3000’
28 2 Free. -
29 2 Free. -
30* 2 Gas Ignition activation delay time. 3 ’’ 0’’..100’
31* 2 Gas valve activation delay time. 1 ’’ 0’’..10’
32* 2 Gas Ignition deactivation delay time. 1 ’’ 0’’..10’
33 2 Fumes control activation time. 0 ’’ 0’’..30’
34 2 IDMT curve time. 36” 0”..3600”
35 2
Delay time between the activation of genset and grid
breakers.
2’ 1'..250”
36 2 Stop failure detection time. 90” 1”..3600”
(*) Only for Gas controllers (CEA7G and CEM7G)
Tabla 2
Measurements Table
Parameter PSW Description
Default
value
Range
1 2
Current transformers conversion factor. Factor com-
mon to RMS current values IR, IS, IT.
100
6
8
10
2
Regulation zero current.
Current reading set to zero.
12 2 Fuel Level Regulation EMPTY.
13 2 Fuel Level Regulation FULL.
Tabla 1
Times Table
Parameter PSW Description
Default
value
Range
1 2 Number of Starts. 4 1..10
2 2
Time between Starts.
Period between starts during which all the outputs
are disabled.
5 ’’ 3’’..15’
3 2
Start Delay.
Time between power failure and engine start.
0 ’’ 0’’..10000’
4 2 Spark Plugs Preheating Time. 0 ’’ 0’’..180’
5 2
Startup Time.
Maximum waiting time before startup has been
achieved. During this period the starting output is
active.
5 ’’ 1’’..30’
6 2
Charging Activation Time.
Time from the moment the starting of the engine is
detected until the activation of the genset contactor.
3 ’’ 1’’..600’
7 2
Nominal condition time.
Time from the moment the starting of the engine
is detected until the quality of the signal generated
begins to be validated.
2” 2”..15”
8 2
Activation time of D+.
At the end of this time, the voltage level at the DI
input will be checked and the D+ output will remain
active or not until the engine stops depending on the
Regulations parameter (3).
3 ’’ 1’’..10’
9 2 Delay time for the activation of EJP1. 1” 1”..1800”
11 2 Cooling Time. 120’ 2’’..1800’
12 2 PE activation time. 10’ 1’’..30’
13 2 Contactor detection time. 5 ’’ 1’’..3000”
14 2
Maximum alarm activation time.
The alarm output is activated (together with the
ashing of the reset and buzzer LED on the display)
when appropriate during this time limit.
15”
0-Indenite
1”..1800”
15 2 Filtering of the RC input. 1.0’ 0.0’’..5.0’
16 2 Filtering of the BPA input. 1.0’ 0.0’’..5.0’
17 2 Filtering of the ATA input. 1.0’ 0.0’’..5.0’
18 2 Filtering of the NA input. 1.0’ 0.0’’..5.0’
19 2 Filtering of the ENT4 input. 1.0’ 0.0’’..120.0’
20 2 Filtering of the ENT5 input. 1.0’ 0.0’’.. 120.0’