Chapter 5 Configuration of Communication parameters
(2) Input items
Input items that can be configured in Ethernet parameters window are shown in
Table 5.6.
Table 5.6 Input items of Ethernet parameters window
No Name Description Range for setting
IP Address Set
1) MAC Address To confirm the MAC address of EH-ETH2 Confirming only
2) IP address To set the IP address of EH-ETH2 Except 0.0.0.0 and 255.255.255.255
3) Subnet mask To set the Subnet mask of EH-ETH2 Between 255.0.0.0 and 255.255.255.248
4) Default gateway To set the Default gateway address of EH-ETH2 Except 255.255.255.255
5) Transfer speed / Type To set transfer speed and type Auto Negotiation (0),
100Mbps Full Duplex (1),
100Mbps Half Duplex (2),
10Mbps Full Duplex (3),
10Mbps Half Duplex (4)
Other station for Diagnosis
6) IP Address To set the destination IP address of EH-ETH2’s testing. Except 0.0.0.0 and 255.255.255.255
7) Port No. To set the destination Port number of EH-ETH2’s
testing.
Between 1 and 65535
Task Code Logical Port No. Set
8) Task Code Port
Timeout
To set the timeout of Task code connection is enable or
not. This value is valid for all Task code connections. If
this is specified as disable, the value of item (9) is not
valid.
Enable (0), Disable (1)
9) Timeout value To set the value for timeout of Task code connection and
this unit is second. This value is valid for all Task code
connections.
Between 0 and 65535
Task code port m (m[1:4])
10-m) Port No. To set the logical port number for Task code connection. Between 1 and 65535
11-m) Protocol To select the protocol for Task code connection. TCP/IP (0), UDP/IP (1)
(3) Operation buttons
The window has the five operation buttons shown below.
Table 5.7 Operation buttons of Ethernet parameters window
Name Description
Online
To connect to EH-ETH2. At this time, the present values are overwrtiten in
each input boxes.
Offline To disconnect from EH-ETH2.
Set To set the values in the input boxes.
Default Set To set the default values.
Close To close the window.
When you click the “Set” button, EH-ETH2 Configurator will check the parameters. If all parameters are
correct, they will be saved into set up file, and the completion massage box will appear. If they are wrong, set
up file is not updated. In this case, please check and correct the value, and set again.
5-9