Phas
e Location PDU Plug
Operating
/ Max
Voltage
Rating
Max
Current
Rating
No. of
CB per
PDU Breaker Rating
Thre
e
3
America
s
PDU-32C
13800F1
0
NEMA L15 30P
3 pole, 4 wir
e
A + B + C +
gnd
208 V
A
C /
240 V
AC
30A per
phase
3
UL489
15A 2 pole
EMEA,
APAC
A3CK-24
3694-50
IEC 309, red
4 pole, 5 wire
A + B + C +
Neut + gnd
400 VAC 32A per
phase
3
UL489
16A 2 pole
Notes:
1
The numbers in this table were taken from the PDU manufacturer’s specications. For
information about PDUs, see
Power distribution units for Hitachi Universal V2 Rack (on
page 153) .
2
Americas: Single phase, 30 Amp PDU
, (12) IEC C13. EMEA/AP
A
C: Single phase, 32 Amp
PDU
, (12) IEC C13; (2) IEC C19 .
3
Americas: Method three phase, 30 Amp PDU, (24) IEC C13; (6) IEC C19. EMEA/APAC:
Minkels three phase, 32 Amp PDU, (24) IEC C13; (6) IEC C19.
Appendix C: Electrical specications
Hitachi Virtual Storage Platform G1000, G1500, and VSP F1500 Hardware Guide 142