Note: Depending on the conguration, the storage system can draw
considerably less power than the rating of the PDU plugs. Use the weight and
po
wer calculator to determine the power draw for a specic system. See
Component power consumption, heat output, and airow (on page 146) or
use the Weight and Power Calculator to calculate the power dr
aw, current
draw, and heat output of a specic system at the following URL:
http://www.hds.com/go/weight-and-power-calculator/.
Table 35 PDU plugs, circuit breakers, and receptacles
Phas
e Location PDU Plug
Operating
/ Max
Voltage
Rating
Max
Current
Rating
No. of
CB per
PDU Breaker Rating
Singl
e
2
America
s
PDU-121
112F10
NEMA L6 30P
twistlock
2 pole, 3 wire
A + B + gnd
208 VAC
30A 2
UL489
16A, 20 A trip
EMEA,
APAC
A3CR-12
3294-51
IEC 309, blue
2 pole, 3 wire
A + B + gnd
230 VAC /
250 VAC
32A 2
UL489
16A, 20 A trip
Appendix C: Electrical specications
Hitachi Virtual Storage Platform G1000, G1500, and VSP F1500 Hardware Guide 141