Figure 18 Service clearances for a four-rack, two-controller system
Table 21 Floor load rating and required clearances for a four-rack, two-controller
system
Floor Load
Rating
(kg/m2)
Required Clearance (a+b) m
c= -0.3 c=0 c=0.2 c=0.4 c=0.6 c=0.8 c=1.0 c=1.4
Over 700 0 0 0 0 0 0 0 0
600 0.1 0 0 0 0 0 0 0
500 0.8 0.4 0.2 0 0 0 0 0
450 1.3 0.8 0.6 0.4 0.2 0.1 0 0
400 1.9 1.4 1.1 0.9 0.7 0.5 0.3 0.1
350 2.9 2.3 1.9 1.6 1.4 1.2 0.9 0.6
Four-rack conguration - two controllers (center)
Chapter 4: Site preparation specications
Hitachi Virtual Storage Platform G1000, G1500, and VSP F1500 Hardware Guide 94