Chapter 4 Explanation of Functions
4 - 131
Register
No.
Function name Function code R/W Monitoring and setting items Data resolution
Register
No.
1236h (Reserved) - - Inaccessible -
1237h (Reserved) - - Inaccessible -
1238h Jog frequency setting A038 R/W "Start frequency" to 999 0.01 [Hz]
1239h Jog stop mode A039 R/W
0 (free-running after jogging stops [disabled during
operation])
1 (deceleration and stop after jogging stops [disabled
during operation])
2 (DC braking after jogging stops [disabled during
operation])
3 (free-running after jogging stops [enabled during
operation])
4 (deceleration and stop after jogging stops [enabled
during operation])
5 (DC braking after jogging stops [enabled during
operation])
-
123Ah (Reserved) - - -
123Bh
Torque boost method
selection
A041 R/W 0 (manual torque boost), 1 (automatic torque boost) -
123Ch Manual torque boost value A042 R/W 0 to 200 0.1 [%]
123Dh
Manual torque boost
frequency adjustment
A043 R/W 0 to 500 0.1 [%]
123Eh
V/F characteristic curve
selection, 1st motor
A044 R/W
0 (VC), 1 (VP), 2 (free V/f),
3 (sensorless vector control)
-
123Fh V/f gain setting A045 R/W 20 to 100 1 [%]
1240h
Voltage compensation gain
setting for automatic torque
boost, 1st motor
A046 R/W 0 to 255 1 [%]
1241h
Slippage compensation gain
setting for automatic torque
boost, 1st motor
A047 R/W 0 to 255 1 [%]
1242h
to1244h
(Reserved) - - Inaccessible -
1245h DC braking enable A051 R/W 0 (disabling), 1 (enabling), 2 (set frequency only) -
1246h DC braking frequency setting A052 R/W 0 to 40000 0.01 [Hz]
1247h DC braking wait time A053 R/W 0 to 50 0.1 [sec.]
1248h
DC braking force during
deceleration
A054 R/W 0 to 70 1 [%]
1249h
DC braking time for
deceleration
A055 R/W 0 to 600 0.1 [sec.]
124Ah
DC braking/edge or level
detection for [DB] input
A056 R/W 0 (edge operation), 1 (level operation) -
124Bh DC braking force for starting A057 R/W 0 to 70 1 [%]
124Ch DC braking time for starting A058 R/W 0 to 600 0.1 [sec.]
124Dh
DC braking carrier frequency
setting
A059 R/W 5 to 120 0.1 [kHz]
124Eh (Reserved) - - Inaccessible -
124Fh Frequency upper limit setting A061 (high) R/W
0 or "maximum frequency limit" to "maximum
frequency"
0.01 [Hz]
1250h
Frequency lower limit setting
A061 (low) R/W
0 or "maximum frequency limit" to "maximum
frequency"
0.01 [Hz]
1251h A062 (high) R/W
1252h
Jump (center) frequency
setting 1
A062 (low) R/W
0 to 40000 0.01 [Hz]
1253h A063 (high) R/W
1254h
Jump (hysteresis) frequency
width setting 1
A063 (low) R/W
0 to 1000 0.01 [Hz]
1255h A064 R/W
1256h
Jump (center) frequency
setting 2
A065 (high) R/W 0 to 40000 0.01 [Hz]
1257h
Jump (hysteresis) frequency
width setting 2
A065 (low) R/W
0 to 1000 0.01 [Hz]
1258h A066 R/W
1259h
Jump (center) frequency
setting 3
A067 (high) R/W 0 to 40000 0.01 [Hz]
125Ah
Jump (hysteresis) frequency
width setting 3
A067 (low) R/W
0 to 1000 0.01 [Hz]
125Bh A068 R/W
125Ch
Acceleration stop frequency
setting
A069 (high) R/W 0 to 40000 0.01 [Hz]
125Dh
Acceleration stop time
frequency setting
A069 (low) R/W
0 to 600 0.1 [sec.]
125Eh A070 R/W