Chapter 4 Explanation of Functions
4 - 130
(v) List of registers (function modes)
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
1201h Frequency source setting A001 R/W
0 (keypad potentiometer), 1 (control circuit terminal
block), 2 (digital operator), 3 (RS485), 4 (option 1), 5
(option 2), 6 (pulse train input), 7 (easy sequence), 10
(operation function result)
-
1202h Run command source setting A002 R/W
1 (control circuit terminal block), 2 (digital operator), 3
(RS485), 4 (option 1), 5 (option 2)
-
1203h Base frequency setting A003 R/W 30 to "maximum frequency" 1 [Hz]
1204h Maximum frequency setting A004 R/W 30 to 400 1 [Hz]
1205h [AT] selection A005 R/W
0 (switching between O and OI terminals), 1
(switching between O and O2 terminals), 2 (switching
between O terminal and keypad potentiometer), 3
(switching between OI terminal and keypad
potentiometer), 4 (switching between O2 and keypad
potentiometer)
-
1206h [O2] selection A006 R/W
0 (single), 1 (auxiliary frequency input via O and OI
terminals) (nonreversible), 2 (auxiliary frequency
input via O and OI terminals) (reversible), 3 (disabling
O2 terminal)
-
1207h to
120Ah
(Reserved) - - Inaccessible -
120Bh
[O]-[L] input active range
start frequency
A011 (high)
R/W 0 to 40000 0.01 [Hz]
120Ch A011 (low)
120Dh
[O]-[L] input active range end
frequency
A012 (high)
R/W 0 to 40000 0.01 [Hz]
120Eh A012 (low)
120Fh
[O]-[L] input active range
start voltage
A013 R/W 0 to "[O]-[L] input active range end voltage" 1 [%]
1210h
[O]-[L] input active range end
voltage
A014 R/W "[O]-[L] input active range start voltage" to 100 1 [%]
1211h
[O]-[L] input active range
start frequency selection
A015 R/W 0 (external start frequency), 1 (0 Hz) -
1212h
External frequency filter time
const.
A016 R/W 1 to 30 or 31 (500 ms filter ±0.1 Hz with hysteresis) 1
1213h
Easy sequence function
selection
A017 R/W 0 (disabling), 1 (enabling) -
1214h (Reserved) - R/W Inaccessible -
1215h
Multispeed operation
selection
A019 R/W 0 (binary), 1 (bit) -
1216h
Multispeed frequency setting
A020 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
1217h A020 (low) R/W
1218h
Multispeed 1 setting
A021 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
1219h A021 (low) R/W
121Ah
Multispeed 2 setting
A022 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
121Bh A022 (low) R/W
121Ch
Multispeed 3 setting
A023 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
121Dh A023 (low) R/W
121Eh
Multispeed 4 setting
A024 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
121Fh A024 (low) R/W
1220h
Multispeed 5 setting
A025 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
1221h A025 (low) R/W
1222h
Multispeed 6 setting
A026 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
1223h A026 (low) R/W
1224h
Multispeed 7 setting
A027 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
1225h A027 (low) R/W
1226h
Multispeed 8 setting
A028 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
1227h A028 (low) R/W
1228h
Multispeed 9 setting
A029 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
1229h A029 (low) R/W
122Ah Multispeed 10 setting A030 (high) R/W 0 or "start frequency" to "maximum frequency" 0.01 [Hz]
122Bh
Multispeed 11 setting
A030 (low) R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
122Ch A031 (high) R/W
122Dh
Multispeed 12 setting
A031 (low) R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
122Eh A032 (high) R/W
122Fh
Multispeed 13 setting
A032 (low) R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
1230h A033 (high) R/W
1231h
Multispeed 14 setting
A033 (low) R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
1232h A034 (high) R/W
1233h
Multispeed 15 setting
A034 (low) R/W
0 or "start frequency" to "maximum frequency"
0.01 [Hz]
1234h A035 (high) R/W