Chapter 2 Installation and Wiring
2 - 14
Terminal layout Inverter model
R
(L1)
S
(L2)
T
(L3)
PD
(+1)
P
(+)
N
(‑)
U
(T1)
V
(T2)
W
(T3)
R0 T0
GG
L700-370LFF
R0 and T0: M4
Ground terminal: M6
Other terminals: M8
L700-370HFF
R0 and T0: M4
Ground terminal: M6
Other terminals: M6
L700-450LFF
L700-450HFF
R0 and T0: M4
Ground terminal: M8
Other terminals: M8
R
(L1)
S
(L2)
T
(L3)
PD
(+1)
P
(+)
N
(‑)
U
(T1)
V
(T2)
W
(T3)
R0 T0
chargelump
GG
L700-550LFF
L700-550HFF
L700-750HFF
R0 and T0: M4
Ground terminal: M8
Other terminals: M8
[Method of enabling/disabling the EMC filter function]
Enabling the EMC filter
Disabling the EMC filter
(factory setting)
Charge lamp
When not using the DCL,
do not remove the jumper
from terminals PD and P.
Ground terminal with
jumper (shaded in the
figure) to enable/disable the
EMC filter function
Jumper connecting
terminals PD and P
[Method of enabling/disabling the EMC filter function]
Enabling the EMC filter
Disabling the EMC filter
(factory setting )
When not using the DCL,
do not remove the jumper
from terminals PD and P.
Ground terminal with
jumper (shaded in the
figure) to enable/disable the
EMC filter function