10.3.5 INTERMITTENT FAN CONTROL
The intermittent fan control during thermo off in Heating mode can be changed
1 Select "Intermittent fan Heat." from the service menu and
press "OK".
The intermittent fan control setting will be displayed.
2 By pressing " "or "", the "Control Type" will be
changed as below.
".... No.1 <---> No.2 <---> No.3 <---> No.1 ..."
Single model Multi model
No 1 Continuous
30 sec ON / 210 sec
OFF repeatedly
No 2
30 sec ON / 210 sec
OFF repeatedly
50 sec ON / 190 sec
OFF repeatedly
No 3
50 sec ON / 190 sec
OFF repeatedly
Continuous
3 Press "OK" to finish the intermittent fan control setting.
The confirmation screen will be displayed.
4 Select "Yes" by pressing " "or "" and press "OK".
The setting will be confirmed and the screen will return to
the service menu.
5 Press " " to return to the normal mode.
NOTE
This setting cannot use during operation.
The intermittent fan control setting will remain
unchanged after the unit is turned off.