4 Electrical Wiring
92
SMGB0064 rev.0 - 08/2011
DSW5: Transmission setting of end terminal resistance
Before shipment, No. 1 pin of DSW5 is set at ON.
In case of having 2 or more outdoor units connected to the same H-link, set for the second unit the pin number 1 of
DSW5 at OFF.
If only one outdoor unit is used, no setting is required.
Function Setting position
Setting before shipment
Cancellation
DSW6: Power source setting
Function (2/2.5/3) HP (4/5/6) HP (8/10) HP
230V
(Setting before shipment)
400V
(setting before shipment)
Jumper lead setting (JP1~6)
Setting before shipment:
JP1 JP2 JP3 JP4 JP5 JP6
1 0 0 1 1 1
N O T E
0: Open
1: Short circuit
The function selection using the jumper lead setting is shown in the table below.
Setting Function Details
JP1 Not used
JP2 Not used
JP3 Not used
JP4 Fixing for Cooling Only
When JP4 is set to “open”, operation mode is xed for cooling. Thermo-ON is avai-
lable only by “COOL” or “DRY” mode at indoor unit.
JP5 Not used
JP5 R407C pipes
When JP6 is set to “open”, existing piping system control is available. High pressu-
re control is performed depending on existing piping strength.