4 Electrical Wiring
97
SMGB0064 rev.0 - 08/2011
4
4.5.2  Wire sizes for ES Series
Field minimum wire sizes for the power source
Model Power Source Max. Current (A)
Power Source Cable Size Transmitting Cable Size
EN60 335-1 (2*) EN60 335-1 (2*)
All Indoor Units (1*)
1~ 230V 50Hz
5 0.75 mm
2
0.75 mm
2
RAS-2HVRN2 11 2.5 mm
2
RAS-2.5HVRN2 18,5 4.0 mm
2
RAS-3HVRNS2 18,5 4.0 mm
2
RAS-4HVRNS2E 26 6.0 mm
2
RAS-5HVRNS2E 26 6.0 mm
2
RAS-6HVRNS2E 26 6.0 mm
2
RAS-4HRNS2E
3N~ 400V 50Hz
13 4.0 mm
2
RAS-5HRNS2E 13 4.0 mm
2
RAS-6HRNS2E 13 4.0 mm
2
RAS-8HRNSE 20 6.0 mm
2
RAS-10HRNSE 23 6.0 mm
2
N O T E
(1*): Except RPI-8.0-10.0
Follow local codes and regulations when selecting eld wires.
The above wire sizes marked with (2*) are selected at the maximum current of the unit according to the eu-
ropean standard, EN60 335-1. Use wires not lighter than the ordinary neoprene (polychloroprene) sheathed
exible cord (code designation H05RN-F).
In the case that the power cables are connected in series, add each unit maximum current and select the wire
sizes in next table.
The ground cable size must comply local code: IEC 245, No. 571.