5  Control System
120
SMGB0064 rev.0 - 08/2011
5.1.2  Device control system for ES Series
Control subject
Purpose
Cooling operation Heating operation Defrost operation
Control frequency of inverter com-
pressor
The frequency control is deter-
mined with the next parameters:
•  Temperature difference be-
tween air inlet temperature and 
setting air temperature.
•  Calculate the width of the 
change by amount of change.
The frequency control is deter-
mined with the next parameters:
•  Temperature difference be-
tween air inlet temperature 
and setting air temperature.
•  Calculate the width of the 
change by amount of change.
Fixed frequency (stop compressor 
during 30 sec). After defrosting 
condition was completed.
Opening degree expansion valve 
of outdoor unit
Fully open
•  Control range of expansion 
valve opening degree is de-
termined to optimize tempera-
ture. on the top of compressor.
Fully open
Opening degree expansion valve 
of indoor unit
•  Control range of expansion 
valve opening degree is deter-
mined to optimize I.U. gas pipe 
temp. (Tg) - I.U. liquid pipe 
temp. (Tl) difference.
•  Specied opening degree at 
normal control starting. After-
ward, controlled to optimize 
I.U. liquid pipe temp. (Tl).
Specied opening degrees control-
led by temp. on the top of com-
pressor. (Td).
Outdoor fan
•  Fan step is operated for O.U. 
liquid pipe temp. (Te) stabiliza-
tion control
•  Fan step is controlled accord-
ing to O.U. liquid pipe temp. 
and temp. on the top of com-
pressor.
Fan stop.
4-Way valve (RVR) OFF ON OFF
Solenoid valve (SVA) 
(Equalised pressure valve)
•  Turn ON at starting 
RAS-(4-10)H(V)RNS(2)E
•  Turn ON at starting 
RAS-(4-10)H(V)RNS(2)E
Turn ON at defrosting
High/Low pressure balance
•  Control by indoor expansion 
valve 
RAS-(2-3) HVRN(S)2
•  Turn ON SVA before compres-
sor starting
RAS-(4-10)H(V)RNS(2)E
•  Control by outdoor expansion 
valve 
RAS-(2-3) HVRN(S)2
•  Turn ON SVA before compre-
sor starting 
RAS-(4-10)H(V)RNS(2)E
—
N O T E
•  I.U.: Indoor unit
•  O.U.: Outdoor unit
•  Tc / Te: Condensing temperature / Evaporating temperature
•  Td: Discharge temperature
•  Tl: Liquid temperature
•  Tg: Gas temperature
•  Cap: Capacity
•  Temp.: Temperature