8 Troubleshooting
260
SMGB0064 rev.0 - 08/2011
Alarm code
42
Heating Overload (High pressure switch will be activated) for ES Series
The RUN LED ickers and “ALARM” is displayed on the remote control switch.
The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit
number and the alarm code are displayed on the display of the outdoor unit PCB.
- Abnormality indication will appear when the protection device is activated during compressor operation at heating
(see Note), with the outdoor unit evaporation temperature higher than 55 °C and the compressor-top temperature
higher than 95 °C.
RAS-(2-3)HVRN(S)2
RAS-(4-6)H(V)RNS2E