4 Electrical Wiring
107
SMGB0064 rev.0 - 08/2011
4
Connection example between H-LINK and H-LINK II units
In case of mixed H-LINK and H-LINK II systems, set H-LINK units in the rst 16 system positions, as shown in the following
gure. There are 42 systems, 16 with FSN1E indoor units type and 26 with FSN3E indoor units type.
N O T E
An H-LINK II is capable of controlling up to 160 indoor units.
If using PSC-5S and CSNET WEB 2.0 (only compatible with H-LINK), take into account that it will only recognize
16 indoor units and 16 outdoor units.