EasyManua.ls Logo

Hitachi RAS-(3-6)HVRNM2E - Electrical Wiring for the Outdoor Unit es Series

Hitachi RAS-(3-6)HVRNM2E
488 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 Electrical Wiring
88
SMGB0064 rev.0 - 08/2011
4.3 Electrical wiring for the outdoor unit ES Series
4.3.1  Electrical wiring connection for the outdoor unit
The correct electrical wiring connection for the outdoor unit is shown below.
1 Insert the power source cables L1 and N (for 230V/50Hz ) and the ground cable into the ring core, coiling them with two
turns and x the cables using the cable tie (accessory). As shown in next gure, do not insert the cables from different
sides into the ring core.
1. N/(L2) Wire.
2. L1 Wire.
2 Connect the power supply source wires L1 and N (for 230V/50Hz) and L1, L2, L3 and N (for 400V/50Hz) to the terminal
board. Connect the ground wire to the plate in the electrical box.
RAS-(2-3)HVRN(S)2 RAS-(4-6)HVRNS2E Model RAS-(8/10)HRNSE
1
2
3
4
5
1
2
3
4
1
2
3
1. Power wires.
2. PCB.
3. Earth terminal.
4. Side cover.
5. Transmission wires.
1. Transmission wires.
2. Transformer.
3. Fuse.
4. Power wires.
1. Transformer.
2. Transmission wires.
3. Power wires.
RAS-(2-3)HVRN(S)2
RAS-(4-6)HVRNS2E
RAS-(8/10)HRNSE
RAS-(4-6)HRNS2E
1 2
1 2
1. Power supply AC230V.
2. Control cable (5 V).
1. Power supply AC400V.
2. Control cable (5V).

Table of Contents

Related product manuals