EasyManua.ls Logo

Hitachi RAS-(3-6)HVRNM2E - Removing “W” Electrical Componets Surface; Removing Other Electrical Components

Hitachi RAS-(3-6)HVRNM2E
488 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 Servicing
371
SMGB0064 rev.0 - 08/2011
10
Removing “W” electrical componets surface
1 Remove the service cover according to the section Removing service cover, see on page 361 in this chapter.
2 Open the P-mounting plate by rotating 90 degrees to the left according to the section Opening electrical box (P-moun-
ting plate), see on page 367 in this chapter.
3 Use a screw driver to push and release the plastic holders retaining the “W” electrical components surface.
D A N G E R
Check that the LED201 (red) located on the “W” surface PCB is OFF when opening the P-mounting plate.
Do not touch the electrical components when LED201 (Red) located on the “W” surface PCB is ON in order to
avoid an electrical shock.
N O T E
Identify the terminal numbers with mark band. When reassembling the terminals have to be connected to the
correct numbers . If incorrectly connected malfunctions or damages will occur.
Check to ensure that the electrical wires will not be caught between the assembled electrical components and
the mounting plates when the “W” electrical components surface is reassembled.
D A N G E R
Identify the terminal numbers with mark band. When reassembling the terminals have to be connected to the
correct numbers. If incorrectly connected malfunctions or damages will occur.
In case of replacing control PCB set all the dip switches as the same position before replacing. If not mal-
function may occur. Refer to the manual attached with the service PCB.
Do not apply strong force to the electric components and PCBs to avoid damage.
Removing other electrical components
1 Remove the service cover according to the section Removing service cover, see on page 361 in this chapter.
2 Open the P-mounting plate by rotating it to the left according to the section Opening electrical box (P-mounting plate),
see on page 367 in this chapter.
3 Check to ensure the LED201 (Red) of the inverter PCB is off when opening P-mounting plate.
4 Remove other electrical components according to the procedure below and the gures on Chapter 10.
D A N G E R
Check that the LED201 (red) located on the “W” surface PCB is OFF when opening the P-mounting plate.
Do not touch the electrical components when LED201 (Red) located on the “W” surface PCB is ON in order to
avoid an electrical shock.
N O T E
Disconnect all the wires connected with the smoothing capacitor (CB CB1 CB2 CA).
The wire has polar characters. Identify the wire mark band and the indication on the smoothing capacitor when
wire connecting.
Remove the two (2) screws xing the smoothing capacitor and remove the smoothing capacitor.
Disconnect all the wires connecting with the magnetic contactor (CMC1).
Remove the two (2) screws xing the magnetic contactor and remove the magnetic contactor.
Remove the four (4) screws xing the reactor and remove the reactor (DCL).
Disconnect all the wires connected with the noise lter (NF1).
Remove the noise lter by clamping the top of the holder (6 portions) with a pincher.
Identify the terminal numbers with mark band. When reassembling the terminals have to be connected to the
correct numbers . If incorrectly connected malfunctions or damages will occur.

Table of Contents