8  Troubleshooting
253
SMGB0064 rev.0 - 08/2011
8
Phenomenon Cause Check item
Action
 (Turn OFF main switch)
Activation of high pressure 
switch due to excessively high 
discharge pressure during 
cooling operation
Insufcient air ow to heat 
exchanger of outdoor unit
Clogging of heat exchanger? Remover clogging
Check for dust on air lter Remove dust
Check the service space Secure service space
Check for speed:
Outdoor fan: cooling
Indoor fan: heating
Replace fan motor if faulty
Excessively high temp. air to 
outdoor unit heat exchanger
Check for hot air near the ceiling Make good circulation
Check for short circuited air Remove short-circuited air
Check for other heat source Remove heat source
Faulty high 
pressure switch
Faulty pressure 
switch
Measure discharge pressure.
Check continuity after decreasing 
of pressure
Replace it if faulty
Insufcient 
contacting
Measure resistance by tester
Repair looseness.
Replace connector
Incorrect 
connection
Check connections Repair connections
Overcharged refrigerant Check cycle operating temp. Charge refrigerant correctly
Mixture of non-condensable gas in 
refrigerant cycle
Check ambient temp. and 
pressure
Recharge refrigerant after vacuum 
pumping
Clogging of discharge piping Check for clogging. Remove clogging
Faulty or malfunction of expansion 
valve
Check for clogging Remove clogging
Check connecting wiring and 
connectors
Replace connector
Check operating sound from coil Replace coil.
Check discharge gas thermistor Replace thermistor
Check attaching state of discharge 
gas thermistor
Reattach thermistor
Liquid line stop valve or gas line 
stop valve are not in operation
Check stop valves Fully open stop valve
Locking up outdoor unit expansion 
valve closure
Check expansion valve actuation
Replace outdoor
expansion valve
N O T E
•  This alarm code is indicated when the outdoor unit protective device is activated by high discharge pressure  
during cooling operation. Accordingly, when this alarm code is indicated, there is high possibility of high  pres-
sure switch actuation and the above troubleshooting actions are based on such cases.