3. Piping work and refrigerant charge
77
SMGB0079 rev.0 - 01/2013
3
Setting of pipe length DSW.
DSW2 setting will be required only when the refrigerant pipe length is shorter than 5 m or longer than 30 m. Pipe length
setting shall be performed as shown below.
(The ■ side in the DIP switch show the position.)
DSW2 on outdoor PCB1
Factory setting
Piping length between 5 m and ℓ(m)
Pipe Length 5 m or shorter Pipe Length 30 m or longer
Pump down refrigerant
When the refrigerant should be collected into the outdoor unit due to indoor/outdoor unit relocation, collect the refrigerant
as follows:
1 Attach the manifold gauge to the gas stop valve and the liquid stop valve.
2 Turn ON the power source.
3 Set the DSW1-1 pin of the outdoor unit PCB at the “ON” side for cooling operation. Close the liquid stop valve and col-
lect the refrigerant.
4 When the pressure at lower pressure side (gas stop valve) indicates -0.01 MPa (-100 mmHg), perform the following
procedures immediately.
• Close the gas stop valve.
• Set the DSW1-1 pin at the “OFF” side (To stop the unit operation).
5 Turn OFF the power source.
C A U T I O N
Measurethelowpressurebythepressuregaugeandkeepitinameasurementhigherthan-0.01MPa.Ifthepres-
sureislowerthan-0.01MPa,thecompressormaybefaulty.