INSTALLATION AND OPERATION MANUAL
ENGLISH
In case that the power cables are connected in series, add each unit maximum current and select according to the next table:
Selection according to
EN60 335-1
Selection according to MLFC
(at cable Temp. Of 60 ºC)
Current i (A) Wire Size (mm²) Current i (A) Wire Size (mm²)
I 6 0.75 I 15 0.5
6 < i 10 1 15 < i 18 0.75
10 < i 16 1.5 18 < i 24 1.25
16 < i 25 2.5 24 < i 34 2
25 < i 32 4 34 < i 47 3.5
32 < i 40 6 47 < i 62 5.5
40 < i 63 10 62 < i 78 8
63 < i
78 < i 112 14
112 < i 147 22
In case that current exceeds 63 A do not connect cables in series
NOTE:
- Follow local codes and regulations when selecting eld wires, Circuit breakers and Earth Leakage breakers
- Use the wires which are not lighter than the ordinary polychloroprene sheathed exible cord (code designation H05RN-F)
Select the main switches in according to the next table:
Model Power Source
Max.
Current
CB
ELB
(no. poles/A/Ma)
All Indoor Units 1~ 230V 50Hz 5A 6A
2/40/30
RAS-3HVRNME
1~ 230V 50Hz
14A 20A
RAS-4HVRNM1E/HVRNS1E 18A/24A 25/32A
RAS-5HVRNM1E/HVRNS1E 26A 32A
RAS-6HVRNM1E/HVRNS1E 26A 32A
RAS-5HRNM1E
3N~ 400V 50Hz
7A 15A
4/40/30RAS-6HRNM1E 11A 15A
RAS-6HRNM1E 13A 20A
ELB: Earth switch; CB: Switch; (*) Except RPI-8/10HP
13.3.3. H-LINK II SYSTEM
NOTE:
The H-LINK II system can not be applied to the cycle with the old
H-LINK model.
1. Application
The new H-LINK II connecting each indoor unit and outdoor unit for
up to 64 refrigerant cycles (up to 160 indoor unit per H-LINKII), and
connecting wires for all indoor units and all outdoor units in series.
2. Specications
- Transmission Wire: 2-Wire
- Polarity of Transmission Wire: Non-Polar Wire
- Maximum Outdoor Units To Be Connected: 64 Units per
H-LINK II system.
- Maximum Indoor Units To Be Connected: 160 Units per
H-LINK II system
- Maximum Wiring Length: Total 1000m (including CS-NET). In
case that the total wiring length is longer than 1000m, contact the
Hitachi dealer.
- Recommended Cable: Twist Pair Cable with Shield, over
0.75mm2 (Equivalent to KPEV-S)
- Voltage: DC5V
NOTE:
Do not make a wiring in a loop.
3. Dip Switch Setting of Indoor PCB and Outdoor PCB
It is required to set dip switches of every indoor unit and outdoor unit.
PMML0197_r0_04-10.indb 35 08/07/2010 9:20:56