EasyManua.ls Logo

Hitachi RCIM-1.0FSN2 - SYSTEM INSTALLATION DIP SWITCH SETTING

Hitachi RCIM-1.0FSN2
314 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36
INSTALLATION AND OPERATION MANUAL
13.3.4.SYSTEM INSTALLATION DIP SWITCH SETTING
Dip Switch Setting of Indoor PCB and Outdoor PCB for H-LINK II
It is required to set dip switches of every indoor unit and outdoor unit and match of the transmission circuit impedance.
Dip Switch Setting Example:
Unit Name of Dip Switch Mark Setting Before Shipment Function
Outdoor
Unit
Refrigerant Cycle
DSW4
RSW1
For setting refrigerant cycle address of Outdoor Unit. Set the DSW4 and
RSW1 not to overlap the setting of other Outdoor units in the same H-
LINK system
Terminating Resistance DSW5
For matching impedance of transmission circuit, set the DSW5 according
to the quantity of outdoor units in the H-LINK system.
Indoor
Unit
Refrigerant Cycle
DSW5
RSW2
For setting refrigerant cycle address of indoor units. Set the DSW5
and RSW2 corresponding to the address of outdoor unit in the same
refrigerant cycle.
Indoor Unit Address
DSW6
RSW1
For setting indoor unit address. Set the DSW6 and RSW1 not to overlap
the setting of other indoor units in the same refrigerant cycle. (If not set,
the automatic address function is performed).
Cycle nº 0
Cycle nº 1
Cycle nº 2
DSW5
Terminating
Resistance
DSW4
Refrigerant Cycle Nº
(Setting for ten digit)
RSW1
Refrigerant Cycle Nº
(Setting for last digit)
Outdoor units
Indoor units
DSW5
Refrigerant Cycle Nº
(Setting for ten digit)
RSW2
Refrigerant Cycle Nº
(Setting for last digit)
DSW6
Indoor unit Address
(Setting for ten digit)
RSW1
Indoor unit Address
(Setting for last digit)
DSW4 RSW1
DSW5 RSW2
DSW6 RSW1
PMML0197_r0_04-10.indb 36 08/07/2010 9:20:58

Table of Contents

Other manuals for Hitachi RCIM-1.0FSN2

Related product manuals