5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
110
Element Optional function
Individual
setting
Settings
Setting conditions Description
C8
Control by the
temperature sensor of the
remote control switch
? NOTE
The remote control
switch shall be installed
in a proper place for
the correct detection of
room temperature by its
temperature sensor.
O
00
Control by the air inlet sensor of
indoor units (factory setting)
This function species the
temperature sensor to be used
as control sensor by the indoor
unit.
01
Control by the temperature sensor of
the remote control switch
02
Control by the average value of the
air inlet sensor of indoor units and
the temperature sensor of the remote
control switch.
(Air inlet + Remote control switch)/2
Control sensor when
a remote sensor is
connected to the THM4
connector in the indoor
unit PCB
? NOTE
The remote sensor shall be
installed in a proper place
for the correct detection of
room temperature.
Model
RPF(I)-FSN2E
O
00, 01,
02
When a remote sensor is connected
to THM4, this remote sensor is used
as control sensor, whichever the
setting for C8
(factory setting C8=00)
Control sensor when
a remote sensor is
connected to the THM4
connector in the indoor
unit PCB
? NOTE
The remote sensor shall be
installed in a proper place
for the correct detection of
room temperature.
Models
RCI-FSR
RCIM-FSRE
RCD-FSR
RPC-FSR
RPI(L/H)-FSRE
RPI-FSN3E(P)E(-f)
RPK-FSR(H)M
00, 02
Air temperature control using
the average value of the air inlet
thermistor and the remote sensor
(factory setting C8=00)
(Air inlet + Remote sensor)/2
01
Air temperature control using the
remote sensor
C9
Not available –
“- -”
permanent
– –
CA
Not available –
“- -”
permanent
– –
Cb
Selection of forced
stoppage logic
X
00
Forced stoppage input: A contact,
normally open contact (factory setting)
This function determines the
logic operation for the forced
stoppage contacts.
01
Forced stoppage input: B contact,
normally closed contact
CC
Not used
–
00
- Use at 00 conditions
01
Only for DX-Interface,
KPI-E4E and KPI-X4E:
High ventilation speed
00
Function disabled
(factory setting)
This function sets the unit to run
in high fan speed regardless
the setting from remote control
switch.
01
Function enabled